Intermittent Cooling Failure Misdiagnosed as Compressor Failure
4-ton Carrier split system, 11 years old
The Problem
Homeowner reported the AC would cool normally for 2–3 hours, then stop producing cold air entirely. A previous contractor had quoted $3,800 to replace the compressor, citing "compressor failure" based on a single pressure reading taken during a non-failure period.
Diagnosis
Joe arrived during an active failure event and performed a full system evaluation under load. Suction pressure was reading 12 PSI — well below the normal 65–75 PSI range — but the compressor itself was drawing correct amperage. This ruled out compressor failure. Further inspection revealed the TXV (thermostatic expansion valve) was sticking closed under heat load, starving the evaporator of refrigerant. The root cause was a partially clogged filter drier restricting flow and causing the TXV to hunt erratically.
Solution
Replaced the TXV and filter drier. Recovered and recharged the system with the correct refrigerant charge verified by superheat and subcooling measurements. Ran the system for 90 minutes post-repair to confirm stable pressures across a full cooling cycle.
Outcome
System has operated without interruption since repair. The actual problem was a sticking TXV under heat load — not a compressor failure.
Technical Notes
TXV failure under heat load is a common misdiagnosis because pressure readings taken during normal operation appear within range. The failure only manifests after the valve body reaches operating temperature — which is why a diagnosis taken at startup will miss it.