AC RepairKillearn Estates, TallahasseeSummer 2024

Intermittent Cooling Failure Misdiagnosed as Compressor Failure

4-ton Carrier split system, 11 years old

The Problem

Homeowner reported the AC would cool normally for 2–3 hours, then stop producing cold air entirely. A previous contractor had quoted $3,800 to replace the compressor, citing "compressor failure" based on a single pressure reading taken during a non-failure period.

Diagnosis

Joe arrived during an active failure event and performed a full system evaluation under load. Suction pressure was reading 12 PSI — well below the normal 65–75 PSI range — but the compressor itself was drawing correct amperage. This ruled out compressor failure. Further inspection revealed the TXV (thermostatic expansion valve) was sticking closed under heat load, starving the evaporator of refrigerant. The root cause was a partially clogged filter drier restricting flow and causing the TXV to hunt erratically.

Solution

Replaced the TXV and filter drier. Recovered and recharged the system with the correct refrigerant charge verified by superheat and subcooling measurements. Ran the system for 90 minutes post-repair to confirm stable pressures across a full cooling cycle.

Outcome

System has operated without interruption since repair. The actual problem was a sticking TXV under heat load — not a compressor failure.

Technical Notes

TXV failure under heat load is a common misdiagnosis because pressure readings taken during normal operation appear within range. The failure only manifests after the valve body reaches operating temperature — which is why a diagnosis taken at startup will miss it.

TXVRefrigerantMisdiagnosisCarrier
DiagnosticsNortheast TallahasseeSpring 2024

Persistent High Humidity in New Construction Despite Functioning AC

3-ton Trane variable-speed system, 2 years old

The Problem

Homeowner in a 2-year-old home complained of 68–72% indoor humidity despite the AC running constantly and maintaining 74°F. Two previous HVAC companies had inspected the system and declared it "working correctly." Mold was beginning to form on window sills.

Diagnosis

Performed a full Manual J load calculation and compared it against the installed equipment. The 3-ton unit was oversized for the 1,850 sq ft home — a 2-ton system was appropriate. An oversized system short-cycles: it reaches the thermostat setpoint quickly without running long enough to dehumidify the air. Additionally, the variable-speed blower had been set to a fixed high-speed profile during installation, further reducing the system's latent (moisture) removal capacity.

Solution

Reprogrammed the variable-speed blower to a low-speed dehumidification profile, extending runtime per cycle. Installed a whole-home dehumidifier integrated with the air handler to handle the latent load the oversized system couldn't manage. Sealed two duct leaks in the attic that were pulling in humid unconditioned air.

Outcome

Indoor humidity dropped to 48–52% within one week. Mold issue resolved. Homeowner avoided a full system replacement that had been suggested by a third contractor.

Technical Notes

Oversizing is one of the most common installation errors in Florida. Builders often upsize equipment to avoid callbacks, but in a humid climate like Tallahassee, a correctly sized system running longer cycles removes far more moisture than an oversized unit that short-cycles.

HumidityOversizingVariable SpeedTraneDuct Leaks
Heat Pump RepairMidtown TallahasseeWinter 2023

Heat Pump Freezing Up in Mild Weather — Defrost Board Failure

2.5-ton Lennox heat pump, 8 years old

The Problem

Homeowner reported the outdoor unit was completely encased in ice during a 45°F day. The system was blowing cold air inside. A competitor had quoted $1,200 to replace the reversing valve, assuming it was stuck in cooling mode.

Diagnosis

Defrosted the unit manually and monitored the defrost cycle initiation. The defrost control board was not triggering the defrost cycle despite the defrost thermostat calling for it. Tested the defrost thermostat — it was functioning correctly and closing at the right temperature. The control board was receiving the signal but not initiating the defrost relay. Confirmed board failure with a jumper test: manually bridging the defrost terminals caused the system to enter defrost mode correctly, proving the reversing valve was fully operational.

Solution

Replaced the defrost control board. Verified defrost cycle timing and completion. Checked refrigerant charge in heating mode — pressures were within spec.

Outcome

System returned to full heating operation same day. The defrost board was confirmed as the sole failure point — the reversing valve was fully operational throughout.

Technical Notes

Defrost board failures are frequently misdiagnosed as reversing valve failures because both present with the same symptom: the unit stays in cooling mode. The diagnostic distinction is straightforward — a jumper test takes under 5 minutes and definitively isolates the board from the valve.

Heat PumpDefrostLennoxMisdiagnosisControl Board